FM-FME
Back to "Products"Synthetic resin insulated, indoor voltage transformers
for 12 kV and 24 kV highest voltage for equipment.
Types FM-24, FME-12, FME-24
Type markings
The letters and numerals applied in type markings have the following meanings:
F – Voltage transformer
M – Synthetic resin insulated
E – Single pole insulated
12, 24 – Highest voltage for equipment
General description
The types FM and FME are of single-phase synthetic resin insulated indoor voltage transformers, manufactured for supplying the voltage coils of measuring instruments, relays and other devices in equipments with highest voltage of 12, 24 kV. The type FME is of single-pole insulated, applicable between phase and earth (earthed), while the type FM is of double-pole insulated, applicable between phase and phase design.
The voltage transformer is composed of primary (high voltage) and secondary (low voltage) windings, wound concentrically on a “C” type core made of cold rolled electrical steel, embedded entirely in synthetic resin insulation. The material of the windings and the terminals is copper. The secondary windings can be for measuring or protective purposes (in the case of type FME also for producing residual voltage) and the combination of the two respectively. The voltage transformers are available with 1 or 2 secondary windings, in the following accuracy classes: windings for measuring 0.5, 1 or 3 (in the case of type FME 0.2), for protection 3P, 6P and for residual voltage 6P.
The voltage transformer comply with the specifications of MSZ EN 60044-2 and EN 60044-2 standards. It is also possible to produce according to other standards differing from the afore-mentioned.
Packing, delivery
The voltage transformer is delivered in a finish suitable for use under normal climatic conditions, packed in corrugated paper box. Upon agreement, the delivery will be made in finish and packing, suitable for the required climatic zone.
Storage
In case of a long-term storage, it is practical, to keep the voltage transformer indoor, in a covered, well ventilated room (storage temperature: –5°C +40°C).
Installation, putting into operation, operation
Before installation the voltage transformer should be checked in order to discover on the surface, or on the terminals any possible damages occurred during the transportation or the storage. In case of any damages further investigation is necessary. Generally the voltage transformer can be mounted in upright position by means of 4 pcs M12 bolts. The fastening to the supporting structure can be accomplished by the help of legs shaped on the bottom of the device. When fixing, it is adviceable to put under the legs a rubber or a rubbercork plate, in order to equalize the accidental unevennesses.
The bus bar can be connected to the high voltage terminal by M10 bolt.
The neutral primary terminal of the type FME is located beside the secondary terminals and the connection to this (system earthing), which should be accomplished according to the current local prescriptions, is possible by an M5 screw. The size of the screw used for the protective earthing is M8. The protective earthing of the voltage transformer is obligatory. The connection to the secondary terminals is achieved by M5 screw. The rating plate can be found on the opposite side to the secondary terminals.
The screws and washers applied on the voltage transformer are protected by hot-dip galvanizing or cadmium plating. The primary and secondary terminal markings on the voltage transformers (on the type FM: A, B, a, b on the type FME: A, N, a, n, da, dn) and the earthing symbol () are painted with high quality, durable indoor paint beside the terminals.
The seconary terminals are covered by a sealable plastic cap.
Before connection, any contamination, occurred during the transportation and storage should be removed, the terminals cleaned and smeared with contact vaseline. Application an overvoltage protection for the voltage transformers suggested.
Operation is possible keeping the prescriptions of the relevant security-, labour- and property-protection directives. Any faults and breakdowns emerging in the Customer’s sphere of interest due to breaching, disobeying the afore-mentioned, exempt the manufacturer from the warranty and guarantee liabilities.
Maintenance
The maintenance consists of works to be done according to the general rules for indoor instruments and discontinuing of the accidental irregularities. These are:
– periodical inspection of the contamination and cleaning, depending on the degree of impurity,
– inspection of the surfaces,
– tightening of the bolts of the primary and secondary connections,
– tightening of the fastening bolts.
State verification
The secondary windings of the voltage transformers in class 0.5 (in case of type FME also in class 0.2) are manufactured in finish suitable for verification. The verification will be made only on special request, in this case it will be accomplished and documented by an official seal or an affixed verification stamp, by the National Office for Measures.
Data to be submitted with the order
– type (e.g. FME-24),
– rated insulation level (e.g. 24/50/125 kV),
– rated primary and secondary voltages (e.g. 20000/v3/100/v3/100/3 V),
– number, accuracy class, output of the secondary windings. (e.g. class 0.5, 30 VA),
– voltage factor (pl.: 1,9Un/ 8h),
– quantity,
– requested term of delivery.
Other or special requirements:
– climatic zone of use other than normal,
– language of the rating plate,
– packing,
– number of pieces and sort of the documentation to be attached.
Warranty period, guarantee
The warranty period is 12 months and otherwise it can also be established upon the mutual agreement of the parties respectively.
All right reserved for subsequent alteration without prior notice.